15kv Max Voltage, 12.47kv Nominal, 1200amp Switchgear Lineup, Outdoor (nema3r)

US $1200

  • Las Vegas, Nevada, United States
  • Nov 14th
We are replacing the SWGR due to a problem with the insulators in the incoming/main section. These issues would occur during large amounts of precipitation and would result in tracking across the insulator. There is no signs of water intrusion, it was concluded that it was occurring due to a "rain forest affect," and was likely attributed to improper set-up/faulty heaters. The customer has decided to replace the gear due to the critical nature/importance of the gear. Please see information below, please email me for drawings of the gear, photos of the gear, and an Infrared Report done in the incoming/main section after the problem occurred. (1) 15kV max voltage, 12.47kV nominal, 1200Amp switchgear lineup, outdoor (NEMA3R) construction, comprised of the following:   1 - Utility metering section - provisions only for utility supplied VT's and CT's, installation by others.   1 - main switch, consisting of: 1 - 1200Amp switch 1 - operating handle 1 - mechanical interlock 1 - 5kVA CPT 1 - Molded case circuit breaker   1 - transition section   4 - feeder sections, each consisting of: 1 - 600Amp switch 1 - operating handle 1 - set of fuses, rated 175E 1 - loss of phase device 1 - set of CT's 1 - shunt trip 1 - heater control circuit NOTE: BUYER MUST PICKUP ITEM AT SELLERS SCHEDULED TIME (NIGHT OF DEC. 2, 2016: WHEN SWGR IS REMOVED).

Directions

Similar products from Electrical breadboards

People who viewed this item also vieved

By clicking "Accept All Cookies", you agree to the storing of cookies on your device to enhance site navigation, analyze site usage, and assist in our marketing efforts.

Accept All Cookies