DS7430/DS7436 Multiplex Expansion Modules Technical Service Note October 23, 2009 Affects: • DS7430 Multiplex Expansion Module • DS7436 Multiplex Expansion Module • DS7400Xi Control Panel 1.0 Issue Removing or connecting the DS7430 or DS7436 Multiplex Expansion Module while the DS7400Xi Control Panel is powered can cause damage to the control panel. 2.0 Symptoms If the control panel is damaged, random mult iplex bus trouble conditions might occur, such as missing device and device restoral condi tions. These conditions might be seen for individual devices or groups of devices. In ca ses where the damage is extreme, the control panel could stop working. 3.0 Prevention Before removing or connecting a DS7430 or DS7436 to the control panel, remove all power (AC and standby battery) from the system. 4.0 Resolution If the control panel is damaged, it must be replaced.
Condition:
New: A brand-new, unused, unopened, undamaged item in its original packaging (where packaging is applicable). Packaging should be the same as what is found in a retail store, unless the item is handmade or was packaged by the manufacturer in non-retail packaging, such as an unprinted box or plastic bag. See the seller's listing for full details. ...